Technical Data
Performance (EN 60770)
| Accuracy @ 25 °C | ± 0.5% F.S. (incl. non-linearity, hysteresis and repeatability) |
|---|---|
| Response time | < 4 ms |
| Medium depth | Minimum range: 1 meter Maximum range: 100 meter See more details in page 3 (part number chart) |
| Overload pressure | 2.0 × F.S. |
| Pressure type | vented gauge |
| Long term stability | ≤ 0.2% F.S./Year |
| Temperature coefficient | ± 0.03% F.S./°C |
Electrical specifications
| Output signal | 4-20mA |
|---|---|
| Supply voltage | 9-30Vdc |
| Polarity protected | yes |
| Short-circuit protected | yes |
| Zero and span adjustment | No |
| Surge protection | No |
Environmental conditions
| Medium temp range | -20 → +85 °C |
|---|---|
| Ambient temp range | -20 → +80 °C |
| Compensated temp range | 0 → +50 °C |
| EMC – Emission | EN 61000-6-3 |
| EMC – Immunity | EN 61000-6-1 |
| Insulation resistance | > 100 MΩ at 250 V |
Mechanical characteristics
| Materials | Diaphragm | Stainless steel 316L | |
|---|---|---|---|
| Housing | Aluminium alloy | ||
| Cable | PU (typical) | PE (optional) | |
| O-ring | FKM / Viton (typical) | EPDM (optional) | |
| Weight | 1.0 – 5.0 kg (depending on cable length) | ||
| Sealing rating | IP 68 (fulfilled together with mating connector) | ||
Dimensions (Unit: mm)
Data Sheet
File Download
Installation and precautionst
- Theinstallation place should be easy to operation and fixing
- Theinstallation place should be away from the inlet as far as possible
- Theinstallation place should be away from the heat source as far as possible
- Theinstallation place should be away from the vibration source as far as possible
- Wheninstallation, the metal probe should sink to the bottom of the container and fixed
Precautions for safety use
- Cleanthe metal probe (sensor) regularly to avoid block the pressure port
- ASS 316L diaphragm is exposed in the front part of the sensor, any artificial touch is not allowed
- Thecable is special waterproof designed, abrasion, puncture, and cut the cable is strictly prohibited
- Thewiring should strict reference to the electrical connection, wrong wiring will cause damage to the sensor